Products
Explosion Proof Flame Arrestor Vent Cage
video
Explosion Proof Flame Arrestor Vent Cage

Explosion Proof Flame Arrestor Vent Cage

In a “stand-alone” tank system, each tank is effectively isolated from the other storage tanks. The most likely ignition sources are external to the tank, and the transmission of a flame among multiple tanks can usually occur only by the spread of an external fire. In such a “stand-alone” system, the Explosion Proof Flame Arrestor Vent Cage is typically mounted at the end of the tank vent pipe (End-of-Line Deflagration Flame Arrester).
Its intended function is to permit normal tank breathing, while preventing the “flash-back” of an unconfined deflagration (a flame front moving in an unrestricted space at speed less than the speed of sound) through the arrester and into the tank’s vapor space. The Explosion Proof Flame Arrestor Vent Cage provides positive protection against an external flame source entering the tank.

 

 

Explosion Proof Flame Arrestor Vent Cage

 

 

The explosion proof flame arrestor vent cage usually used together with the flame arrestors, breather valves, it is a very important part for the pipeline safety system.

 

We are the professional manufacturer for all kinds of the storage tank and pipe line fittings, such as the flame arrester, breather valve, filters...... which are suitable for flammable gas storage tank or transport pipeline.

 

Our products follow the ISO16852 standards for testing and manufacturing, CE certification. Through the national special equipment inspection and Research Institute of the full type test, resistance to fire performance is excellent, to obtain TSG certification.

 

We have already produced the maximum diameter of the pipe flame arrester 24 inch, product performance was widely recognized petrochemical enterprises. And our products were exported to all over the world.

 

The explosion proof flame arrestor vent cage was specifically developed for vessels which are not pressurized and store Ethanol or other alcohols. The combustion of alcohol requires a modified flame arrester element design to provide protection against endurance burning. In addition, the device provides protection against atmospheric deflagration. Main application area is on suction and vent lines, for inland navigation vessels and on shore systems with the goal to prevent flame transmission caused by endurance burning or atmospheric deflagration.

1


The explosion proof flame arrestor vent cage consists of a housing (1), a weather hood (2) and the flame arrester unit (3). During normal operation the metal weather hood is in a closed position. If a stabilized flame burns on the flame arrester element surface, the fusible link (5), located in a center position, will melt and let the spring loaded weather hood move into the open position. The flame arrester unit consists of two discs (4), which are installed in a casing.

The explosion proof flame arrestor vent cage is available for hydrocarbons for explosion group IIB3 (MESG ≥ 0,65 mm) and alcohols.

The standard design can be used for operating temperatures up to +60°C / 140°F.

EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.


 

Specification

 

 

Model

PTQM

Explosion Group

BS 5501: IIA IIB IIC

Size

DN40-200 GB81-59 PN0.6-2.5 FF,RF

Temperature

CS : -30℃ ~ + 350℃ SS : -80℃ ~ + 480℃

Body Material

L2 A3 304 304L 316 316L

Jonit Type

Flange / Threaded / Butt Welding

Trim Material

304 304L 316 316L

Flanges

HG GB SH HGJ JB ANSI JIS

Bolt/Nut

20# 304 304L 316 316L

Manufacture Inspection

GB5908-86 SY7511-87

Diaphragm (P/V)

NBR PTFE Metal Gasket

Coating

CS : Paint

SS : natural color

product-1003-523

DN (mm)

40

50

80

100

150

Inch

1 1/2

2

3

4

6

Length

180

180

210

250

290

Height

160

160

125

155

175

 

 

ProductsTesting Standard

 

Flame Arrester Valve Testing Standard
Test Conditions
Unless otherwise specified, the tests outlined in this chapter should be conducted under normal atmospheric conditions, which are defined as follows:

a) Ambient temperature: 15°C to 35°C;

b) Relative humidity: 45% to 75%;

c) Atmospheric pressure: 86 kPa to 106 kPa.
 

 

Products Features

 

 

Parallel plate element design provides significant mechanical strength while minimizing pressure drop
Weatherhood protects against environmental conditions
Automatic condensate drainage mitigates freezing and clogging

 

 

Product application

 

 

The explosion proof flame arrestor vent cage is used for urban industrial and mining enterprises ,gas stations ,and it's an important accessory .usually use at below conditions:
(1) transport inflammable gas and flammable gas pipeline
(2) storage petroleum and petroleum product tank
(3) with explosion insecure system vent-pipe
(4) oil and gas recycling system
(5) regenerative boiler burning gas pileline net
(6) gas engine exhaust system
(7) torch system

Hot Tags: explosion proof flame arrestor vent cage, China explosion proof flame arrestor vent cage manufacturers, suppliers, factory, In Line Detonation Flame Arrestor, Pipe Line Flame Arrester, Storage Tank Flame Arrester, In Line Deflagration Flame Arrester, Drawer Type Flame Arrester, Anti Explosion Flame Arrester